Supply | |
---|---|
Rated voltage | 7.2 V DC , battery operated |
Electrical specifications | |
Output rated operating current | 4 ... 20 mA |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V |
Input | |
Connectable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode |
Current | 4 ... 20 mA |
HART communication | |
Output | |
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables |
Transfer characteristics | |
Accuracy | current input: 0.125 % of measuring range |
Influence of ambient temperature | current input: 5 µA/K |
Indicators/settings | |
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization |
Directive conformity | |
Electromagnetic compatibility | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. |
Conformity | |
Degree of protection | IEC 60529 |
Ambient conditions | |
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz |
Corrosion resistance | acc. to ISA-S71.04-1985, severity levelG3 test setup and execution acc. to EN60068-2-60 |
Mechanical specifications | |
Degree of protection | IP66 |
Material | plastic |
Mass | approx. 750 g |
Dimensions | 91 x 88.5 x 100.6 mm (3.6 x 3.5 x 4 inch) (without cable glands and antenna) |
Mounting | mounting on field device , panel or pole mounting versions see type code |
Data for application in connection with hazardous areas | |
EC-Type Examination Certificate | BVS 11 ATEX E 081 , for additional certificates see www.pepperl-fuchs.com |
Directive conformity | |
International approvals | |
IECEx approval | BVS 11.0061 |
Accessories | |
Designation | battery W-BAT-B2Или отправьте нам запрос наnnection with hazardous areas (order separately) mounting set W-ACC-MKF8 |